"Input points: 16 points.
Rated input voltage, frequency: AC100 ~ 120V, 50/60Hz.
Rated input current: 8.2mA (AC100V, 60Hz), 6.8mA (AC100V, 50Hz).
Response time: 20ms.
Common way: 16 point / public end.
Interrupt function: have.
External wiring connection mode: 18 point screw terminal.
The input and output module is the interface between the switch, sensor, actuator, and other control system of the ON/OFF signal processing.
Compared with the previous series, iQ-R MELSEC series of input and output modules have more features,
1 modules can be used for a variety of purposes, to help reduce the cost of deployment and maintenance costs.
The module design of the pursuit of convenience".
Paste the white label on the input module and paste the red label on the output module,
The rated specifications are clearly marked on the front of the module, which can prevent the use of errors.
The input and output number stamped on the top of the front display input and output module LED, can easily confirm the status of the ON/OFF.
The terminal arrangement of each signal is recorded on the wiring terminal of the 16 point module, and the false wiring can be prevented.
The 64 point module can be 32 points as the unit, through the switch to switch to display the input and output number.
In addition, serial number tag in the front of the module, can be easily recognized. "
Differential input, transistor (drain type) output.
Channel number: 2CH.
External wiring connection mode: 40 pin connector
Count input signal: there
Single phase input (single frequency / double frequency)
Dual phase input (single frequency and double frequency /4)
CW/CCW input: there
The signal level (phi A, Phi B): EIA standard RS-422-A differential line driver level MITSUBISHI RX10.
PWM output function can be output through the highest frequency of 200kHz, minimum ON 100ns width of the PWM waveform of any duty cycle
RX10
In addition, the output cycle and duty cycle can be changed when the output PWM,
The use of the most suitable for the use of continuous PWM signal flow control. "The length of the cable: 5 meters MITSUBISHI RX10.
IQ-R MELSEC series of "inter module synchronization", refers to the module can be in accordance with the synchronization cycle between modules,
The function of the input and output time synchronization of the multiple input and output modules and the intelligent function modules of the synchronization object.
Using this function, the system and equipment can be controlled with high precision MITSUBISHI RX10.
In addition, it is also available in the CC-LinkIE field network synchronous communication, so that the action time between the network nodes to maintain synchronization,
To avoid the error caused by the network transmission delay time, so as to build a stable system.
At the same time using these features, it can be easy to respond to the requirements of the high accuracy of the movement of the situation,
For example, the cutting and bending process of offset press, etc.. "Output points: 64 points.
Output form: Transistor (drain type) output.
Rated open and close voltage, current: -.
Rated load voltage: DC12 ~ 24V.
Max load current: 0.2A/ point.
Response time: 1ms.
Common way: 32 point / public end.
Protection function (overload, overheat).
External wiring connection: 40 pin connector two.
Output module with mechanical relay contact mechanism,
Including the load voltage range of the relay and can be used for the output of the DC12~24V load trannsistor output type RX10.
According to the load voltage, the output points of different, choose the most suitable user needs of the module.
Preventive maintenance based on the life of relay contact.
Relay output module can accumulate the number of OON of each output point RX10.
Through the understanding of the relay contacts of the number of times, according to the relay life of preventive maintenance.