RD62D2 | MITSUBISHI High speed counter module RD62D2
MITSUBISHI RD62D2 Manual And Instructions
RD62D2 datasheetPDF datasheet

MITSUBISHI RD62D2 Product information and technical parameters:
Brand: MITSUBISHI
Name: High speed counter module
Model: RD62D2
Differential input, transistor (drain type) output.
Channel number: 2CH.
External wiring connection mode: 40 pin connector
Count input signal: there
Single phase input (single frequency / double frequency)
Dual phase input (single frequency and double frequency /4)
CW/CCW input: there
The signal level (phi A, Phi B): EIA standard RS-422-A differential line driver level.
PWM output function can be output through the highest frequency of 200kHz, minimum ON 100ns width of the PWM waveform of any duty cycle.
In addition, the output cycle and duty cycle can be changed when the output PWM,
The use of the most suitable for the use of continuous PWM signal flow control.

The input power supply voltage: AC100 ~ 240V.
Input frequency: 50/60Hz plus or minus 5%.
Input maximum apparent power: 120VA.
Maximum input power: -.
Rated output current (DC5V): 3.5A.
Rated output current (DC24V): 0.6.
IQ-R MELSEC series consists of CPU module, power module, substrate module, input and output module, intelligent function module and so on MITSUBISHI RD62D2.
For the entire system, the substrate module can be expanded to 7 levels, up to 64 modules can be installed,
Therefore, large scale system can be constructed RD62D2 In addition, by using the RQ extended substrate module,
The sea can also effectively use the MELSEC-Q series of modules of the asset. "10Mbps Max., master / local station, support Ver MITSUBISHI RD62D2. 2 CC-Link.
CC-Link is a bus (RS-485) - type open field network which can control and information processing at the same time.
Can be in the CC-Link and high-speed transmission of ON/OFF information from the station equipment, such as bit data, analog information, such as digital data.
Connect all kinds of field equipment through CC-Link.
Can connect all kinds of support CC-Link field equipment, according to various control requirements to build the corresponding system MITSUBISHI RD62D2.
Use remote device network mode, up to 64 remote equipment such as analog devices, etc.. Analog input channel number: 8CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C:-.
Temperature coefficient: positive and negative 35ppm/.
Common
Conversion speed: 10ms.
Insulation between channels: isolation transformer insulation.
Absolute maximum input: positive and negative 15V, 30mA.
External wiring connection mode: 40 pin connector.
Voltage input
The analog input voltage: DC - 10 - 10V.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: DC0 ~ 20mA.
Digital output value: 0 ~ 32000.
Analog input module for the external analog signal into the interface of the programmable controller.
Can choose the channel between the insulation, voltage input, current input, voltage / current mixed input, thermocouple input, temperature resistance (RTD) input for a variety of purposes, such as modules.
Filter high frequency interference.
Analog input module has been equipped with a first order lag filter.
The analog input signal with high frequency interference component can be obtained by using the first order lag filter.
Parameters can be set through the filter time constant, no program can be easy to use.
Execute event driven progrram through alarm output
Strengthen the implementation of the interrupt function according to the alarm output flag, easy to carry out preventive maintenance RD62D2.
The measured value and the change rate of the analog input signal exceed the upper and lower limits of the set,
Regardless of the procedure of the scan time, can be executed interrupt handling, quickly respond to abnormal conditions RD62D2.