R60AD8-G datasheetPDF datasheet

MITSUBISHI R60AD8-G Product information and technical parameters:
Brand: MITSUBISHI
Name: Analog input module
Model: R60AD8-G
Analog input channel number: 8CH.
accuracy
Ambient temperature of 25 plus or minus 5 degrees C: plus or minus 0.1%.
Ambient temperature 0 ~ 55 degrees C:-.
Temperature coefficient: positive and negative 35ppm/.
Common
Conversion speed: 10ms.
Insulation between channels: isolation transformer insulation.
Absolute maximum input: positive and negative 15V, 30mA.
External wiring connection mode: 40 pin connector.
Voltage input
The analog input voltage: DC - 10 - 10V.
Digital output value: 32000 ~ 32000.
Current input
Analog input current: DC0 ~ 20mA.
Digital output value: 0 ~ 32000.
Analog input module for the external analog signal into the interface of the programmable controller.
Can choose the channel between the insulation, voltage input, current input, voltage / current mixed input, thermocouple input, temperature resistance (RTD) input for a variety of purposes, such as modules.
Filter high frequency interference.
Analog input module has been equipped with a first order lag filter.
The analog input signal with high frequency interference component can be obtained by using the first order lag filter.
Parameters can be set through the filter time constant, no program can be easy to use.
Execute event driven program through alarm output
Strengthen the implementation of the interrupt function according to the alarm output flag, easy to carry out preventive maintenance.
The measured value and the change rate of the analog input signal exceed the upper and lower limits of the set,
Regardless of the procedure of the scan time, can be executed interrupt handling, quickly respond to abnormal conditions.

10Mbps Max., master / local station, support Ver.2 CC-Link.
CC-Link is a bus (RS-485) - type open field network which can control and information processing at the same time.
Can be in the CC-Link and high-speed transmission of ON/OFF information from the station equipment, such as bit data, analog information, such as digital data MITSUBISHI R60AD8-G.
Connect all kinds of field equipment through CC-Link R60AD8-G
Can connect all kinds of support CC-Link field equipment, according to various control requirements to build the corresponding system.
Use remote device network mode, up to 64 remote equipment such as analog devices, etc.. Memory capacity: 256MB.
As one of the specific features of the iQ-R CPU series MELSEC module, the new C language controller module is added MITSUBISHI R60AD8-G.
C language ARM developed a multi-core controller can perform multiple programs simultaneously based on.
In addition, both the robustness and timing of the C language controller can also be used as a substitute for computer / computer platform.
Moreover, the C language controller adopts a non fan structure, and does not raise dust, and is most suitable for use in a clean environment such as a micro chip factory MITSUBISHI R60AD8-G.
Play iQ-R MELSEC series of high performance, flexible, strong characteristics, can be used in a variety of industrial applications to achieve automation.
Can be simple to use 3 kinds of tool software.
C language controller has been installed in a variety of drivers embedded real-time OS. Various modules can be easily accessed through a special function,
No need to develop the driver and install new OS, through a special function to access a variety of modules,
Can be simple to deploy, reduced cost of development.
You can use CW Workbench and CW Configurator (software) (setting and monitoring tools) and CW-Sim (simulation tool VxWorks.),
Provide strong support for C language program development.
Can be easily programmed, no restrictions on the microprocessor.
By using the C language controller module specific function (CCPU function), MELSEC communication function (MD function),
Can easily access the C language controller module, I/O module, intelligent function module, network module, programmable controller CPU and sports CPU, etc.,
Create an application that uses a programmable controller device.
Coonfigurator CW can be used for parameter setting, diagnosis and monitoring R60AD8-G.
Using Configurator CW,
The iQ-R/Q MELSEC series module (network module, intelligent function module, input and output module, etc.) can be easily set, diagnosis, moonitor and test by the C language controller module R60AD8-G.
The operation of Configurator CW is similar to that of iQ-R MELSEC programming software Works3 GX.


...More relevant models >>>>